Chapter 4: Dialer programming

FSC Series Technical Reference Manual

53

Setting system event transmit options

Table 18 lists the set of system event transmit options and their default values.

Review Table 18 and change values as required. If you don’t need to make any
changes, go to “Setting IDC event transmit options“ on page 54.

Table 18: System event transmit options

Option Description

Values

CS Test Rcvr

Determines where the dialer transmits a
test signal when the control panel is in the
normal state

CS 1, CS 2, CS 1 & 2, or None

Default: CS 1

CS AB Tst Rcvr

Determines where the dialer transmits a
test signal when the control panel is in an
abnormal state

CS 1, CS 2, CS 1 & 2, or None

Default: CS 1

Walk Tst Rcvr

Determines where the dialer transmits an
event code when the control panel is
placed in walk test mode

CS 1, CS 2, CS 1 & 2, or None

Default: CS 1

Drill Rcvr

Determines where the dialer transmits an
event code when notification appliance
circuits are manually activated

CS 1, CS 2, CS 1 & 2, or None

Default: None

Reset Rcvr

Determines where the dialer transmits an
event code when the control panel is reset

CS 1, CS 2, CS 1 & 2, or None

Default: CS 1

Prog Mode Rcvr

Determines where the dialer transmits an
event code when the control panel is
placed in program mode

CS 1, CS 2, CS 1 & 2, or None

Default: CS 1

Dialer Dis Rcvr

Determines where the dialer transmits an
event code when the dialer is disabled

CS 1, CS 2, CS 1 & 2, or None

Default: CS 1

Panel Sil Rcvr

Determines where the dialer transmits an
event code when the control panel is
silenced

CS 1, CS 2, CS 1 & 2, or None

Default: None

Signal Sil Rcvr

Determines where the dialer transmits an
event code when notification appliance
circuits are automatically or manually
silenced

CS 1, CS 2, CS 1 & 2, or None

Default: None

Gnd Flt Rcvr

Determines where the dialer transmits an
event code when the control panel detects
an earth ground connection

CS 1, CS 2, CS 1 & 2, or None

Default: CS 1

Low Batt Rcvr

Determines where the dialer transmits an
event code when the battery voltage is
between 19.4 and 21.4 VDC

CS 1, CS 2, CS 1 & 2, or None

Default: CS 1