Appendix D

Panel specifications

Table 30: Panel specifications

Three-zone

control panel

Five-zone
control panel

Ten-zone
control panel

Initiating device
circuits (IDCs)

Class

B

3

5 3 1 10

8 6 4 2 0

Class

A

0

0 1 2 0 1 2 3 4 5

Notification
appliance circuits
(NACs)

Class

B

2

2 0 4 2 0

Class

A

0

0 1 0 1 2

Power supply

4.25 A total

4.25 A total

4.25 A (expandable to 7.5 A total)

NAC voltage rating

Regulated 24 VFWR

Maximum NAC current

2.0 A each
3.5 A total

2.0 A each
3.5 A total

2.0 A each
3.5 A total, 7.0 A with optional
power expander transformer

AC input 120 V, 60 Hz

1.2 A

1.25 A

2.2 A (includes optional power
expander transformer)

Base panel current draw
(standby)

96 mA

104 mA

128 mA

Base panel current draw
(alarm)

180 mA

224 mA

242 mA

Battery placement

Up to two 7 Ah batteries will fit in the
control panel. Use a BC-3 battery
cabinet to install batteries larger than 7
Ah.

Up to two 18 Ah batteries will fit in
the control panel. Use a BC-3
battery cabinet to install batteries
larger than 18 Ah.

Maximum auxiliary current

0.5 amps

Auxiliary output

24 VDC, Regulated

IDC max. detector standby
current

3.0 mA per circuit. See compatibility list P/N 3101019 for a list of approved
detector models and quantities

IDC circuit

Maximum loop resistance: 26 Ω
Maximum loop capacitance: 0.03 µF