Chapter 3: Panel programming

FSC Series Technical Reference Manual

41

NAC Class:

Determines if the NAC is wired Class A, Class B.

Automatic Sig Silence:

Determines how long NACs stay on after an alarm

event before they are automatically silenced. Select between 0 minutes (NACs
stay on indefinitely) and 30 minutes.

NAC Silenceable:

Determines if the NAC can be silenced.

Table 13: NAC program options

Step Option

Values

LCD first line

ALARM

TROUBLE

SUP

POWER

DISABLE

LCD second line

WATERFLO

W

ANN TROUBL

E

BATT TROUBLE

GND FAULT

SERVICE DETECTOR

21

NAC Types [2]

    Continuous

   

Temporal

(3-3-3)

   

GENESIS

(default)

  

GENESIS

(AV

Sil)

   

Coder

   

City

Tie

   

22

NAC Class [3]

   

Class B (default)

   

Class

A

   

23

Auto Sig Silence [4]

   

0 minutes (default)

   

1

minute

   

2

minutes

   

3

minutes

  

4

minutes

   

5

minutes

   

6

minutes

   

7

minutes

  

8

minutes

   

9

minutes

   

10

minutes

   

11

minutes

  

12

minutes

   