FSC Series Technical Reference Manual

23

Figure 7: Typical auxiliary/booster power supply wiring

In addition, remember to do the following:

• Configure the auxiliary/booster power supply’s trouble relay to close only on

AC power failures. Refer to the power supply‘s installation instructions for
more infomation.

• Use an initiating device circuit to monitor the auxiliary/booster power supply’s

trouble relay. Set the IDC’s zone type for AC Fail.

• Wire the AUX power common on the auxiliary/booster supply to the AUX

power common on the F-Series control panel.

+

RST+

IDC+
IDC–

NAC/AUX+
NAC/AUX–

TROUBLE COM

NO

NC

24V AUX RISER

(greater than 0.5 A)

24V AUX RISER
(0.0 to 0.5 A)

Auxiliary/booster power supply

F-Series control panel

4.7 kΩ
EOLR