Replacing the control panel fuse – Edwards Signaling FSC Series User Manual

Page 74

Advertising
background image

Chapter 5: Maintenance

66

FSC Series Technical Reference Manual

Message Possible

cause

Battery Bad

The battery is bad and needs to be replaced.

Battery Missing

The battery is no longer connected.

AC Failure

The panel lost AC power.

Charger Trouble

The panel detected a battery charger trouble condition. The
charger may not be able to charge the batteries.

Ground Fault

The panel detected a ground fault.

Transformer 2 TR

The panel detected a trouble condition in the Power Expander
Transformer.

AUX Power Troub

The panel detected a trouble condition in the AUX power circuit.

Internal Comm TR

There panel lost communications with an F-DACT(F).

RRM(s) disabled

One or more FSRRM24s are disabled.

Dialing...

The F-DACT(F) is dialing a DACR.

DACT Configuration TRBL

The F-DACT(F) is not programmed or has unverified changes.

DACT Delivery TR

The F-DACT(F) failed to deliver a message to the receiver or
CMS.

DACT Line 1 Trbl

A ground fault or line fault has been detected on Line 1 of the
F-DACT(F).

DACT Line 2 Trbl

A ground fault or line fault has been detected on Line 2 of the
F-DACT(F).

Note:

If the Disabled and Annunc Trouble LEDs are on, and all IDC and NAC Disabled LEDs are

off, then the FSRRM24 is disabled.

Replacing the control panel fuse

WARNING:

High voltage capable of causing personal injury or death may be

present. Make sure all sources of power are removed from the panel before
replacing the fuse.

The control panel is protected with a 5 A fuse. The fuse is part of the AC terminal
block located inside the control panel.

To replace the fuse:

1. Disconnect the standby batteries, then switch off the circuit breaker that

supplies mains AC power to the control panel.

2. Open the cabinet door, then remove the terminal block cover from its slot to

expose the AC terminal block.