Configuring the panel – Edwards Signaling FSC Series User Manual

Page 39

Advertising
background image

Chapter 3: Panel programming

FSC Series Technical Reference Manual

31

Step Option

Values

LCD first line

ALARM

TROUBLE

SUP

POWER

DISABLE

LCD second line

WATERFLO

W

ANN TROUBL

E

BATT TROUBLE

GND FAULT

SERVICE DETECTOR

was XX now 05

   

was XX now 06

   

was XX now 07

  

was XX now 08

   

was XX now 09

   

was XX now 10

   

was XX now 11

  

was XX now 12

   

was XX now 13

   

was XX now 14

   

Configuring the panel

To configure the panel, assign values to the panel program options as indicated
in Table 11. Record your settings on the panel programming worksheet in
Appendix B.

Follow this general sequence of steps:

1. Restore the panel default settings.

2. If passcode protection is required, enable the passcode. You should also

change the passcode from its default value.

3. Starting with Panel Operating Mode, enter a value for each option. You can

skip an option if its default value is acceptable.

4. Detect which remote modules are connected to the control panel.

The panel program options are described below.

Panel Op Mode:

Determines the basic operation of the control panel. The values

that you can select are: