Edwards Signaling FSC Series User Manual

Page 60

Advertising
background image

Chapter 4: Dialer programming

52

FSC Series Technical Reference Manual

Table 17: Dialer options

Option Description

Values

Line 1 Dialing

Determines whether LINE 1 is connected
to a touch tone phone system or a rotary
dial phone system

Tone or Pulse

Default: Pulse

Line 1 Supv Dur [1] Determines how long the dialer waits

before reporting a line cut or ground fault
(if selected) on LINE 1

0 to 200 seconds. 0 turns line
supervision off.

Default: 200 seconds.

Line 2 Dialing

Determines whether LINE 2 is connected
to a touch tone phone system or a rotary
dial phone system

Tone or Pulse

Default: Pulse

Line 2 Supv Dur [1] Determines how long the dialer waits

before reporting a line cut or ground fault
(if selected) on LINE 2

0 to 200 seconds. 0 turns line
supervision off.

Default: 200 seconds.

Blind Call Dial

Determines whether the dialer can dial out
without waiting for a dial tone

Yes or No

Default: No

Line GF Check [2] Determines whether LINE 1 and LINE 2

are supervised for ground faults

Yes or No

Default: Yes

Tx Test Time

Determines when the dialer transmits a
test signal

00:00 (midnight) to 23:59
(11:59 p.m.)

Default: 2:17 a.m.

Tx Tst Frequency
[3]

Determines how often the dialer transmits
a test signal

00 to 45 days

Default: 01 (daily)

Rings to Answer

Determines how many rings it takes before
the dialer answers

01 to 15

Default: 05

Ring Type

Determines the ring pattern that the dialer
recognizes

Any or Normal (2 seconds on,
4 seconds off)

Default: Any

Callback Enable

Determines whether the callback security
feature is enabled

Yes or No

Default: No

Callback #

The telephone number that the dialer dials
out when the callback security feature is
enabled

0 to 9, A, B, asterisk (*), pound
sign (#), and comma (,) up to
20 characters

Default: Blank

[1] To meet UL 864 9th edition requirements, set Line 1 Supv Dur and Line 2 Supv Dur to a value
between 1 and 200.

[2] To meet UL 864 9th edition requirements, set Line GF Check to Yes.

[3] To meet UL 864 9th edition requirements, set Tx Tst Frequency to 01.

Advertising