Edwards Signaling FSC Series User Manual

Page 97

Advertising
background image

Appendix B: Programming templates

FSC Series Technical Reference Manual

89

IDC 1 events


Event


Account

Contact ID
event code

4/2 event
act. code

4/2 event
rest. code

Alarm zone active

None 

1

2

1 & 2

(1/3)11000001

11 E1

Waterflow zone active

None 

1

2

1 & 2

(1/3)13000001

21 EA

Trouble

None 

1

2

1 & 2

(1/3)37300001

71 F1

Supervisory zone active

None 

1

2

1 & 2

(1/3)20000001

31 E1

Monitor zone active

None 

1

2

1 & 2

(1/3)40000001

5A EA

Notes

1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.

IDC 2 events


Event


Account

Contact ID
event code

4/2 event
act. code

4/2 event
rest. code

Alarm zone active

None 

1

2

1 & 2

(1/3)11000002

12 E2

Waterflow zone active

None 

1

2

1 & 2

(1/3)13000002

22 E2

Trouble

None 

1

2

1 & 2

(1/3)37300002

72 F2

Supervisory zone active

None 

1

2

1 & 2

(1/3)20000002

32 E2

Monitor zone active

None 

1

2

1 & 2

(1/3)40000002

52 E2

Notes

1. Default values are shown in bold.
2. You must use the FSCU to change Contact ID event code and 4/2 event restoration code values.
3. The Contact ID event code is preceded with a 1 for event activations and a 3 for event restorations.

Advertising