Chapter 1: System overview and operation

FSC Series Technical Reference Manual

9

Notes

• You can install remote modules separately or combined in the same electrical

box. For example, a system with a ten-zone control panel typically has one
FSRSI and two FSRZI-SAs installed in a 3-gang electrical box.

• The FSRSI includes a buzzer that sounds a temporal (3-3-3) pattern when

there is an active alarm zone, a slow pulse pattern when there is an active
supervisory zone, and an intermittent pattern when there is a system trouble.

FSRA10(F) and FSRA10C(F) controls and

indicators

Figure 3: Location of the controls and indicators on the remote annunciators

Table 6: Descriptions of the remote annunciator controls and indicators

Item Name

Description

1

Zone active LEDs

Red indicates an active alarm zone. Yellow indicates an
active supervisory zone. Flashing yellow indicates an active
monitor zone.

2

Zone trouble LEDs

On indicates a zone trouble.

3

Power LED

On indicates the control panel has AC power.

4

Fire Alarm LED

On indicates an active alarm zone.

5

Supervisory LED

On indicates an active supervisory zone.

Lamp Test

Power
Fire Alarm
Supervisory
Ground Fault
Trouble

Signal Silence

& Drill

Reset

Ack/Silence

1
2

3

4 5 6

8

9

10

11

7