Chapter 3: Panel programming

28

FSC Series Technical Reference Manual

If you have a dialer, the selected option is displayed on the first line of the LCD. If
not, the option is indicated on the top row of status LEDs.

In the programming instructions that follow, when you see “select the
<option_name> option,” press Signal Silence & Drill or Remote Disconnect until
the option is displayed on the LCD or indicated on the status LEDs.

Entering values for panel options

Use the Panel Silence, Walk Test, and Reset buttons to enter values for the
selected panel option. Pressing the Panel Silence button selects the next value.
Pressing the Walk Test button selects the previous value. Pressing the Reset
button enters the selected value.

If you have a dialer, the selected value is displayed on the second line of the
LCD. If not, the value is indicated on the bottom row of status LEDs.

In the programming instructions that follow, when you see “enter <value>,” press
the Panel Silence or Walk Test buttons until the value is displayed on the LCD or
indicated on the status LEDs then press Reset.

When entering a set of numbers:

1. Press the Panel Silence or Walk Test buttons to increase or decrease the

number.

2. Press the Reset button to enter the number and position the cursor at the

next number.

If the number doesn’t need to be changed, press Reset to go to the next number.

SIGNAL

SILENCE

& DRILL

REMOTE
DISCON-

NECT

NEXT

OPTION

PREVIOUS

OPTION

PANEL

SILENCE

WALK

TEST

NEXT

OPTION

PREVIOUS

OPTION

RESET

ENTER