Installing the f-dact(f), Nfpa 72 compliance requirements – Edwards Signaling FSC Series User Manual

Page 29

Advertising
background image

Chapter 2: Installation

FSC Series Technical Reference Manual

21

Installing the F-DACT(F)

The F-DACT(F), also called the dialer, is a digital alarm communicator transmitter
(DACT). The dialer transmits event activation and restoration codes to a
compatible digital alarm communicator receiver (DACR) over standard loop-start
telephone lines. The dialer is capable of split reporting to two different accounts
and telephone numbers.

In addition to the dialer functions, the F-DACT(F) provides:

• An alphanumeric LCD to display system messages and programming

prompts

• An event history log of panel and DACT events, viewable through compatible

software

Note:

The F-DACT(F) modem is only rated for 2400 baud communication.

Some PC modems may not be compatible with this baud rate.

• A modem for uploading and downloading panel configuration, history, and

current status to a PC running compatible software

The F-DACT(F) can be programmed to operate as a single- or dual-line
DACT/Modem/LCD display, a Modem/LCD display, or an LCD display only.

NFPA 72 compliance requirements

For the dialer to be NFPA 72 CS compliant, the following conditions are required:

• The factory installed warning label must be removed from the F-DACT(F)’s

LINE 2 phone jack.

• A second phone line, independent of that used for line one must be

connected to the F-DACT(F)’s LINE 2 phone jack.

• The F-DACT(F) must be programmed to transmit a test signal at least once

every 24 hours.

In addition, NFPA 72 requires that you perform a reacceptance test after you
make any changes to the panel programming (also called the site-specific
software). See NFPA 72 National Fire Alarm Code for testing requirements.

For additional download security, the F-DACT(F) can be programmed to perform
a callback function.

Advertising