Genesis II Installation Instructions

Page 108

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

5-3.3.5 Multiple Network Arrangement

Figure 5-4 shows a multiple network arrangement consisting, effectively, of four separate networks.

Each is wired in a bus topology and each could be up to 400 metres long (at the default 57,600 Baud

Rate) or 1,000 metres long (at the optional 9,600 Baud Rate).

The networks are linked by the electronics in the Innotech Repeater IR12 module. The GENII MPI

Modem and Printer Interface does not need to be an isolated version but it should be noted that the

Comms cable connecting the Innotech Repeater IR12 module will be earthed through the MPI via the

PC and the printer.

Fit EOL

Jumper

Fit EOL

Jumper

5-3.4 REM Network End of Line Termination (EOL)

All REM’s have EOL jumpers and these must be fitted correctly. See the Figure 5-5

through to

Figure

5-8

. There are many variations to network layouts the following four examples provide a guide to

correct jumper application.

Example Figure 5-5:

This example shows a Genesis II Direct Digital Controller with a straight forward network of REMs.

See Note

See Note

See Note

Repeater

2

1

See Note

2

1

2

1

PC

Repeater

Repeater

Figure 5-4:  Multi-Network Arrangement

Maximum Cable length is 400 metres at 57,600 Baud Rate (Default) and 1,000 metres at 9,600 Baud Rate.

NOTE

Both ends must have EOL jumpers fitted.

NOTE

Figure 5-5:  Example of a Simple REM Network