Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 3 – Electrical Installation

END OF

CABLE

JUMPER

RS485

COMMS

CONNECTIONS

POWER

3-4.11 GENII CS REM Control Station Module

The GENII CS REM Control Station Module is powered by 24VAC ±10% @ 50/60Hz. Power Consumption

is 3 VA maximum.

The GENII CS REM mounts into a standard electrical wall plate. The only connections to the GENII

CS REM are 24VAC power and the RS485 Comms link. Locations of electrical terminals are shown in

Figure 3-15, which is a rear view of the module.

When all connections have been made, protect the module from dirt and moisture by covering it with

plastic but do not mount the module in the wall plate until commissioning is completed. This is to

allow addresses to be set as part of the commissioning process.

Figure 3-15:  GENII CS REM Control Station Module