4.8 genii pi rem pulse input module, Genii pi rem pulse input module, Genii pi rem pulse input signal conditions – Innotech Genesis II Digital Controller (v5) User Manual

Page 58: E 3-12

Advertising
background image

Genesis II Installation Instructions

Page 58

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

3-4.8 GENII PI REM Pulse Input Module

The GENII PI REM Pulse Input Module (Figure 3-12) is powered by 24VAC ±10% @ 50/60 Hz. Power

Consumption is 4 VA maximum.

The GENII PI REM provides 5 opto isolated digital inputs to sense pulsed signals from field equipment.

The voltage detection range is 12 to 24VDC. The GENII PI REM detects pulses with a minimum on time

of 20ms, with a minimum off time of 20ms, which gives a maximum of 25 pulses per second.

R

GENESI S

PULSE INPUT

Remote Expansion Modul

e

1 2 3

A B C D E F G H I J

RS485 COMMS

CONNECTIONS

END OF

CABLE

JUMPER

POWER

DIGITAL

INPUT

CONNECTIONS

+DI1- +DI2- +DI3- +DI4- +DI5-

The RS485 Comms connection block is in the upper right section of the module and the End of Cable

Jumper is next to it.

Digital Input terminals are located at the bottom of the module; input signal connections are listed in

Table 3-18.

Figure 3-12:  GENII PI REM Pulse Input Module

Active

Reference

Terminal

Signal

Terminal

Signal

A

DI 1 +

B

DI 1 -

C

DI 2 +

D

DI 2 -

E

DI 3 +

F

DI 3 -

G

DI 4 +

H

DI 4 -

I

DI 5 +

J

DI 5 -

Table 3-18: 

GENII PI REM Pulse Input Signal Conditions

Advertising