1.2.4 - internal-source digital inputs – Innotech Genesis II Digital Controller (v5) User Manual

Page 82

Advertising
background image

Genesis II Installation Instructions

Page 82

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

4-1.2.4 Internal-Source Digital Inputs

The GENII DI REM provides eight dry contact (voltage-free) inputs to sense contact closure from

field equipment. The eight digital inputs are connected to terminals A through H (see

Figure 4-3

).

Contacts I and J are signal common terminals. The REM provides 5VDC between each input and

common. This voltage is shorted to common when the switch is closed. Check the digital input

wiring as follows:

1. Tag and disconnect the RS485 Comms cable(s) from the RS485 Comms Connector at the upper-

right corner of the REM. The cable shields may be left connected if desired.

2. Apply 24VAC operating power to the GENII DI REM. Power off other units.

3. Set the digital voltmeter range to read at least 5.0VDC.

4. Connect the voltmeter between the first digital input channel (Terminal A) and the associated

switch common (Terminal I or J). Observe polarity, ensuring the red (+) test lead is connected to

Terminal A and the black (-) test lead is connected to the switch common terminal.

5. Observe the voltmeter. It should indicate 5VDC with the input switch open.

Avoid risk of electrical shock observe all local electrical safety requirements when performing the nest step.

CAUTION

• Digital outputs are controlled by relays within the associated Genesis unit. These relays are connected to the

external circuits that can contain up to 24VAC.

• Procedures in this manual require checking these circuits with power applied. To avoid death or serious injury by

electrical shock, use extreme caution when working with energised circuits and follow precautions in this manual.

• Checks are to be performed only by qualified, licensed electricians who are familiar with local safety procedures.

Under no circumstances should anyone other than a qualified electrician perform these checks.

CAUTION

6. Manually close the input switch. If that is not practical, connect a short jumper wire across the

contacts.

7. Observe the voltmeter. It should indicate 0VDC with the input switch closed.

8. Release the manually-closed contacts. If a jumper wire was used in Step 6, remove the jumper

wire.

9. Repeat Steps 4 through 8 for the remaining digital input channels.

10. Remove operating power from the REM.

11. Reconnect the RS485 cable that was disconnected in Step 1.

Advertising