1.4 set jumper plugs, Units requiring jumper settings – Innotech Genesis II Digital Controller (v5) User Manual

Page 91

Advertising
background image

Page 91

Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 4 – Commissioning

4-1.4 Set Jumper Plugs

Various jumper plugs throughout the system must be set properly before power can be applied to the

system.

There are 4 categories of jumper plug:

Address Plugs set the address of each Remote Expansion Module

• Analogue Output plugs are used to select either Variable or Heat Valve Mode of operation for

analogue outputs. Refer to section

3-3.1.5

for a definition of Variable and Heat Valve Modes.

• End-of-Cable jumpers provide the proper termination impedance for the RS485 Comms Cable. It is

installed in the last unit of the cable run

• Frequency Plugs set the frequency of each wireless Remote Expansion Module or Interface

The computer-generated wiring diagram (

Figure 4-5

) shows the locations and required settings for

each address jumper and analogue output jumper.

Table 4-4 is provided as an aid for properly setting the various jumper plugs. The table lists

the required jumper setting, the types of jumper plugs and the reference paragraph containing

instructions for setting them for each Genesis II unit.

Terminal

Address

End of Cable

Analogue Output

Frequency

See Paragraph:

4-1.4.1

4-1.4.2

4-1.4.3

4-1.4.4

GENII DDC Digital

Controller

Yes

MPCII Mid Points

Controller

Yes

GENII AI REM

Yes

Yes

GENII AO REM

Yes

Yes

Yes

GENII DI REM

Yes

Yes

GENII DO REM

Yes

Yes

GENII IDI REM

Yes

Yes

GENII PI REM

Yes

Yes

GENII MZS REM

Yes

Yes

GENII MZSAH REM

Yes

Yes

GENII CS REM

Yes

Yes

GENII CSAH REM

Yes

Yes

GENII CSFCAH REM

Yes

Yes

GENII MP REM

Yes

GENII MP405 REM

Yes

GENII MP414 REM

Yes

GENII MP423 REM

Yes

GENII MP432 REM

Yes

GENII WMI

Yes

SENRx

Yes

Yes

Table 4-4: 

Units Requiring Jumper Settings

Advertising