Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 3 – Electrical Installation

3-4.7 GENII IDI REM Opto Isolated Digital Input Module

The GENII IDI REM Opto Isolated Digital Input Module (Figure 3-11) is powered by 24VAC ±10% @

50/60Hz. Power Consumption is 4VA maximum.

The GENII IDI REM provides 5 opto isolated digital inputs to sense signals from field equipment. The

voltage detection range is 12 to 24 volts AC or DC.

R

GENESI S

ISOLA TED DIGI TA L I NPUT

Remote Expansion Modul

e

1 2 3

A B C D E F G H I J

RS485 COMMS

CONNECTIONS

END OF

CABLE

JUMPER

POWER

DIGITAL

INPUT

CONNECTIONS

+DI1- +DI2- +DI3- +DI4- +DI5-

Active

Reference

Terminal

Signal

Terminal

Signal

A

DI 1 +

B

DI 1 -

C

DI 2 +

D

DI 2 -

E

DI 3 +

F

DI 3 -

G

DI 4 +

H

DI 4 -

I

DI 5 +

J

DI 5 -

Table 3-17: 

GEN II IDI REM Opto Isolation Digital Input Signal Conditions

Figure 3-11:  GENII IDI REM Opto Isolated Digital Input Module