Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 4 – Commissioning

4

42 43 44 45 46 47 48

NO

NO

C

V

AC

V

DC

0V

+

-

V

AC

V

DC

240V

+

-

0V

24V

AC/DC

GENESIS II

DIGITAL

CONTROLLER

TERMINALS

EXTERNAL

DEVICE

RELAY

ON

RELAY

OFF

NO C NO C

24V

AC/DC

0V

4-1.2.6 Checking Analogue Input Wiring

The analogue input wiring for the following Genesis units should be checked as part of the

commissioning process:

• GENII DDC Digital Controller

• MPCII Mid Points Controller

• GENII AI REM

Checking analogue input wiring requires special consideration due to the wide variety of analogue

input devices that may be used in the system. Some input devices function as signal voltage sources;

some devices function in the loop current mode and others provide resistive inputs to the Genesis

unit. For this reason there is no single procedure that can be used on all analogue inputs.

Procedures presented in this manual are based on identifying the type of Analogue Input Signal

Conditioner (AISC) assigned to each analogue input channel. Since each analogue input device

requires a specific AISC type to match the signal to the Genesis unit, the type of AISC assigned to

an analogue input channel indicates the type of input signal and the range. The various types of

AISCs are listed in

Table 4-3

along with the type of analogue signal and the range. Reference to the

paragraph containing the instructions for checking the input wiring is also provided in

Table 4-3

.

Figure 4-4:  Checking Digital Output Wiring