Current value is determined by measuring voltage across a resistor in series.

NOTE

AISC Model

Input Type

Parameter

Measured

Expected Value

Reference

Paragraph

DO5

Digital

Voltage

0 or 5VDC

4-1.2.7

D33

Digital

Voltage

0 or 10VDC

4-1.2.7

IO5

0 - 5mA Passive

Current (see Note) 0 - 5mA

4-1.2.8

I20

4 - 20mA Passive

Current (see Note) 4 - 20mA

4-1.2.8

P20

Loop Powered

Inspect Wiring

N/A

4-1.2.8

TD1

Current Loop

Current (see Note) 0- 250µA

4-1.2.8

TD2

0 - 500µA

Current (see Note) 0 - 500µA

4-1.2.8

TH1

Thermistor

Resistance

0 - 1kΩ

4-1.2.9

TH2

Thermistor

Resistance

0 - 2kΩ

4-1.2.9

TH3

Thermistor

Resistance

0 - 3.8kΩ

4-1.2.9

TH4

Thermistor

Resistance

0 - 8.2kΩ

4-1.2.9

TH5

Thermistor

Resistance

0 - 16.2kΩ

4-1.2.9

TH6

Thermistor

Resistance

0 - 33.3kΩ

4-1.2.9

TH7

Thermistor

Resistance

0 - 68.1kΩ

4-1.2.9

TH8

Thermistor

Resistance

0 - 121kΩ

4-1.2.9

TH9

Thermistor

Resistance

0 - 221kΩ

4-1.2.9

V05

Voltage

Voltage

0 - 5VDC

4-1.2.7

V10

Voltage

Voltage

0 - 10VDC

4-1.2.7

Table 4-3: 

Analogue Input Checks