3-3.1.3 Digital Outputs

Each of the Genesis II Direct Digital Controller’s twelve digital output channels (Terminals 42–65)

consists of a single-pole, double-throw (SPDT) relay. The two terminals assigned to each channel

represent the associated relay’s Normally Open (NO) and Common (COM) contacts.

Digital output relay contacts are rated at 24VAC, 2A. Good practice is to use pilot relays for the actual

switching functions, particularly when it applies to inductive loads such as coils, solenoids and

motors. This protects the relays of the Digital Output channel and has the advantage of allowing the

pilot relays to be installed adjacent to the controlling switch-gear.

Refer to Table 3-4 for Digital Output terminal number assignments.

Normally Open (NO)

Common (COM)

Terminal

Signal

Terminal

Signal

42

DO 1 NO

43

DO 1 COM

44

DO 2 NO

45

DO 2 COM

46

DO 3 NO

47

DO 3 COM

48

DO 4 NO

49

DO 4 COM

50

DO 5 NO

51

DO 5 COM

52

DO 6 NO

53

DO 6 COM

54

DO 7 NO

55

DO 7 COM

56

DO 8 NO

57

DO 8 COM

58

DO 9 NO

59

DO 9 COM

60

DO 10 NO

61

DO 10 COM

62

DO 11 NO

63

DO 11 COM

64

DO 12 NO

65

DO 12 COM

Table 3-4: 

Genesis II DDC Output Signal Conditions