Use of genii mpi, circuit 2, E 5-18 – Innotech Genesis II Digital Controller (v5) User Manual

Page 120

Advertising
background image

Genesis II Installation Instructions

Page 120

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

A better solution is to use an MPI that has RS485 isolation ICs and to fit a GENII 485I Isolated RS485

Comms card to the local Digital Controller and earth the screen at the first Digital Controller in

Control Panel No. 2, as shown in Figure 5-18 below.

Figure 5-18:  Use of GenII MPI, Circuit 2