5. With the voltmeter still connected, manually close the input contacts. If it is not possible to

close the circuit manually, connect a jumper wire across the contacts at the switching device, as

shown in Figure 4-2.

6. Ensure the voltmeter indicates the proper signal voltage as listed in

Table 4-2

.

7. Ensure that the voltmeter indicates the correct polarity. The unit will not operate properly if the

signal polarity is incorrect.

8. Release the manually closed contacts or remove the temporary jumper from the switch

contacts.

9. Repeat Steps 3 through 7 for the remaining digital input channels.

Avoid risk of electrical shock observe all local electrical safety requirements when performing the nest step.

CAUTION

Figure 4-2:  Checking Digital Input Wiring