4.15 genii mp414 rem multipoint module, Genii mp414 rem multipoint module, E 3-19 – Innotech Genesis II Digital Controller (v5) User Manual

Page 66: Mp414

Advertising
background image

Genesis II Installation Instructions

Page 66

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

3-4.15 GENII MP414 REM Multipoint Module

The Innotech GENII MP414 REM Multipoint Module is a remote expansion device that has both input

and output expansion capabilities. The GENII MP414 REM provides relay outputs for distributed

control, digital inputs for status detection and Thermistor inputs for temperature measurement.

The GENII MP414 REM (Figure 3-19) is powered by 24VAC ±10% @ 50/60Hz, or powered by 24VDC ±15%.

Power Consumption is 4 VA maximum.

Inputs:

• 10 kΩ thermistor temperature sensor.

• 4 x 24VAC or DC Isolated switched contact digital inputs.

Outputs:

• 4 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp

Inductive.

• 1 x Analogue Output, 0-10VDC ±0.05V into > 2 kΩ load.

C

O

N

TR

O

L

S

Y

S

TE

M

S

A

U

S

TR

A

L

IA

®

MP414

NOTE:

24V AC /DC

ALL OUTPUT RELAYS:-

Rated at :

16Amp R esistive

6Amp Inductive

Com = Common Contact

NO = Normally Open Contact

ANALOGUE OUTPUT:-

Rated at :
0-10VDC into >2 k Loa d

(Voltage Free Contacts by other)

DIGI TA L I NPUT S

+24V

0V

DI#+

DI#-

NOTE:

ALL DIGITAL INPUTS:-

Ra ted at :

24V (AC or DC)

(Voltage Free Contacts by other)

TYPICAL DIGI TA L I NPUTS

+24V

SENSOR

C+
C-

S2

S1

Comms

24V AC or DC Supply

0V AC or DC Supply

0V

EARTH

D

I 4

D

I 1

D

I 2

D

I 3

+
-

Comm

s

Jum

pers

A2

A1

A0

TERM

SHLD2

SHLD1

TH2

TH1

+

-

+

-

+

-

+

-

Com

NO

D

O

1

+

AO

-

1

D

O

2

D

O

3

D

O

4

0

V

24V

Com

NO

Com

NO

Com

NO

E

D

I 4

D

I 1

D

I 2

D

I 3

+
-

Comms

Jumper

s

A2

A1

A0

EOL

SHLD2

SHLD1

TH2

TH1

+

-

+

-

+

-

+

-

The RS485 Comms connection block is in the lower-left section of the module (as illustrated above)

and the End of Cable Jumper is next to it.

The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing

addresses or adding or removing cabling from the terminals.

IMPORTANT

Figure 3-19:  GENII MP414 REM Multipoint Module