3-4.18 GENII WMI Wireless Module Interface

The Innotech GENII WMI Wireless Module Interface is a remote expansion for the Genesis II Direct

Digital Controller or MPCII Mid Points Controller. The GENII WMI provides an interface to the SENRx

series of wireless temperature sensors.

The GENII WMI (Figure 3-22) is powered by 24VAC ±10% @ 50/60Hz. Power Consumption is 4 VA
maximum.

There are no inputs or outputs on a GENII WMI. It is designed to receive the input data from any
SENRx modules located up to 20 metres away (depending on obstructions).

The RS485 Comms connection block is in the upper right section of the module and the End of Cable

Jumper is next to it (Figure 3-22).

The Cable run between the Genesis II Direct Digital Controller and GENII WMI, or MPCII Mid Points

Controller and GENII WMI, should not exceed 600 metres. The Comms wiring requires cable especially

suited for RS485. Other shielded cable is not suitable and may cause spasmodic Comms failures.

The GENII WMI should be mounted within a 20 metre radius (depending on obstructions) of all SENRx

modules from which it will be receiving data (

Figure 3-23

). The location should be dry, clean and free

of excess vibration.

GENII WMI modules operate within the 2.4-2.5 GHz worldwide unlicensed Industrial-Scientific-Medical

(ISM) frequency band.

There are four jumpers located in a row on the GENII WMI, labelled F0, F1, F2 and F3. These select

the frequency channel to use within the 2.4-2.5 GHz range. Typically, these jumpers need only be

changed if multiple GENII WMIs are used, or in areas with poor reception or strong interference.

Figure 3-22:  GENII WMI Wireless Module Interface

• The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when

changing addresses or adding or removing cabling from the terminals.

• The frequency jumpers on the GENII WMI must exactly match the frequency jumpers on any SENRx modules to be

communicated with.