Genesis II Installation Instructions

Page 112

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

When there is more than one connection point to earth the screen becomes a conductor and no

longer performs correctly. Care should be taken to ensure only one bonded earth point is ever

connected on a primary network Refer Section

5-3.5.4

for details on use of a Repeater in a primary

network.

5-3.5.2 Continuous Screen

The screen on a primary network needs to be continuous. That means it remains unbroken along its

entire length. As there is one ‘S’ terminal on a typical primary network device both the Global and

Net screens are to be connected to this tie terminal.

Refer to Figure 5-10 and Figure 5-11 for examples of Genesis II Direct Digital Controller / MPCII Mid

Points Controller Comms Terminal connections.

5-3.5.3 Primary Network Connections

Figure 5-10:  Example of Comms Screen Connection

Figure 5-11:  Typical Comms Network Connections