Innotech repeater ir11 and ir12, E 5-12, Repeater – Innotech Genesis II Digital Controller (v5) User Manual

Page 114

Advertising
background image

Genesis II Installation Instructions

Page 114

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

5-3.5.4 Innotech Repeater Modules

The Innotech Repeater modules IR11 and IR12 (Figure 5-12) can be used with both the Genesis II

Direct Digital Controller and MPCII Mid Points Controller. The repeater’s function is to rebuild each

data byte before retransmitting it.

When a repeater is added to a network it effectively creates two separate networks.

This means users must apply all the rules to each side of the repeater as if they were actually two

completely separate networks. All primary network rules apply without variation. All repeaters do

have Soft Earth features. They do not negate the need for a hard earth on either side of the repeater

network sections. It is not recommended to earth both ports (1 & 2) right at the repeater as this

would defeat some of the advantages of the port isolation. Port 2 (remote port) should always be

earthed on the remote side.

IR11 Single Channel Innotech Repeater Module

Repeater

PW

R

A0

24V AC or DC Supply
0V AC or DC Supply (Earthed)
RS-485 [Shield]

RS-485 [-]

RS-485 [+]

RS-485 [Shield]

RS-485 [Shield]

RS-485 [-]

RS-485 [+]

RS-485 [Shield]

RS-485 (Port 1)

RS-485 (Port 2)

RS-485

End of Line

Terminators

0

V

24V

POR
T

1

P 1
P 2

E

O

L

SHLD2

-
+

POR
T

2

-
+

SHLD1

SHLD2

SHLD1

Flash Upgrade Enable

Power ON

Comms Port 1/Channel 2 (REM-SSG)

Comms Port 2/Channel 2 (REM-SSG)

P1

-2

P2

-2

IR12 Dual Channel Innotech Repeater Module

Repeater

RS-485 GBL 1 [-]

RS-485 [Shield]

RS-485 NET 1 [+]

RS-485 GBL 1 [+]

RS-485 NET 1 [-]

PW

R

A0

RS-485 GBL 2 [-]

RS-485 [Shield]

RS-485 NET 2 [+]

RS-485 GBL 2 [+]

RS-485 NET 2 [-]

24V AC or DC Supply
0V AC or DC Supply (Earthed)

(NET Port 1)

(GLOBAL Port 1)

RS-485

End of Line

Terminators

(GLOBAL Port 2)

(NET Port 2)

0

V

24V

GB
L

1

NET

1

N

G

EOL

G

N

EOL

SHLD

+
-

+
-

GB
L

2

NET

2

SHLD

+
-

+
-

RS-485

End of Line

Terminators

Flash Upgrade Enable

Power ON

Comms Port 1/Channel 1 (GBL)

Comms Port 2/Channel 1 (GBL)

P1

-2

P2

-2

P1

-1

P2

-1

Comms Port 2/Channel 2 (NET)

Comms Port 1/Channel 2 (NET)

Figure 5-12:  Innotech Repeater IR11 and IR12

Advertising