Genesis II Installation Instructions

Page 54

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

The RS485 Comms connection block is in the upper right section of the module and the End of Cable

Jumper is next to it.

Analogue Output terminals are located at the bottom of the module; output signal connections are

listed below in Table 3-14. Analogue Output cables should be run using twisted pair shielded cable.

The screens should be connected to the signal’s negative output terminal (B, D, F, H or J) in each case.

3-4.5 GENII DI REM Digital Input Module

The GENII DI REM Digital Input Module (Figure 3-9) is powered by 24VAC ±10% @ 50/60 Hz. Power

Consumption is 4VA maximum.

The GENII DI REM provides 8 dry contact closure switches (inputs provide 5VDC that is shorted to

common when the input is closed) to sense contact closures from field equipment.

Terminal

Signal

Terminal

Signal

A

AO 1+

B

AO 1-

C

AO 2+

D

AO 2-

E

AO 3+

F

AO 3-

F

AO 4+

H

AO 4-

I

AO 5+

J

AO 5-

Table 3-14: 

GENII AO REM Analogue Output Signal Conditions

Figure 3-9:  GENII DI REM Digital Input Module