3-4 Wiring of Remote Expansion Modules

The following paragraphs contain wiring information for the following types of Remote Expansion

Modules (REMs) used in the Genesis II System:

• GENII AI REM Analogue Input Module

(

3-4.3

)

• GENII AO REM Analogue Output Module

(

3-4.4

)

• GENII DI REM Dry Contact Digital Input Module

(

3-4.5

)

• GENII DO REM Digital Output Module

(

3-4.6

)

• GENII IDI REM Opto Isolated Digital Input Module

(

3-4.7

)

• GENII PI REM Pulse Input Module

(

3-4.8

)

• GENII MZS REM Multi Zone Station Module

(

3-4.9

)

• GENII MZSAH REM Zone Control Station A/H

(

3-4.10

)

• GENII CS REM Control Station Module

(

3-4.11

)

• GENII CSAH REM Control Station After Hours Module

(

3-4.12

)

• GENII CSFCAH REM Control Station Fan Control, After Hours Module (

3-4.13

)

• GENII

MP405

Multipoint

Module

(

3-4.14

)

• GENII

MP414

Multipoint

Module

(

3-4.15

)

• GENII

MP423

Multipoint

Module

(

3-4.16

)

• GENII

MP432

Multipoint

Module

(

3-4.17

)

• GENII

Wireless

Module

Interface

(

3-4.18

)

• SENRx Wireless Temperature Sensors

(

3-4.19

)

Communication between the Genesis II Direct Digital Controller or MPCII Mid Points Controller and

REMs is by way of a RS485 cable connected between the dedicated REM network socket on the digital

controller and the REM network.

The method for connecting the modules to electrical power and to the RS485 Comms cable system

is similar for most of the different types of modules, except where otherwise noted. The following

two paragraphs provide detailed instructions for connecting electrical power and the RS485 system,

respectively.

3-4.1 REM Power Connections

Power requirements are 24VAC, ±10% at 50/60 Hz. Refer to the appropriate paragraph below for the

physical location of the power connection block within each type of REM. At the power connection

block, the 24VAC power terminals are:

• Terminal 1 = 24VAC Supply

• Terminal 2 = 0VAC Supply

• Terminal 3 = Earth

Terminal 3 is for the protection of the RS485 Comms circuitry and must be connected to a good,

electrically bonded earth. This may be the earth bus bar of the switchboard or the point that

connects the chassis of the equipment the module is located in. This connection is independent of

and in addition to the earthed AC Neutral at Terminal 2.

Do not connect Terminal 3 to Terminal 2.

CAUTION