Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 3 – Electrical Installation

3-3.2.6 REM Connector

The MPCII Mid Points Controller has the facility for I/O expansion using Remote Expansion Modules

(REMs). Each REM provides an array of points which can be connected to a sub network up to 600

metres in length.

The fifteen REMs can be made up of any mix of the available types with one exception - the MP REM.

The MP REM can only be addressed between 1 and 8 and only 8 MP REMS can be used.

The REM connector is a 4 way terminal connection that provides access between the MPCII Mid Points

Controller and the expansion modules.

The individual REMs are connected to the device by means of an RS485 Comms cabling arrangement,

as explained below in

3-4 Wiring of Remote Expansion Modules

.

Refer to Table 3-12 for Analogue Output terminal number assignments:

Screen Terminals, located between the Analogue Output terminals AO 2 and AO 3 on the MPCII Mid Points

Controller, are provided for terminating Analogue Output Cable Screens.

NOTE

Terminal

Signal

Terminal

Signal

AO 1

AO 1+

38

AO 1-

AO 2

AO 2+

39

AO 2-

Screen

Common

40

Common

Screen

Common

41

Common

AO 3

AO 3+

42

AO 3-

AO 4

AO 4+

43

AO 4-

Table 3-12: 

MPCII Mid Points Controller Analogue Outputs