4.17 genii mp432 rem multipoint module, Genii mp432 rem multipoint module, E 3-21 – Innotech Genesis II Digital Controller (v5) User Manual

Page 70

Advertising
background image

Genesis II Installation Instructions

Page 70

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

3-4.17 GENII MP432 REM Multipoint Module

The Innotech GENII MP432 REM Multipoint Module is a remote expansion device that has both input

and output expansion capabilities. The GENII MP432 REM provides relay outputs for distributed

control, digital inputs for status detection and Thermistor inputs for temperature measurement.

The GENII MP432 REM (Figure 3-21) is powered by 24VAC ±10% @ 50/60Hz, or powered by 24VDC

±15%. Power Consumption is 4 VA maximum.

Inputs:

• 10kΩ thermistor temperature sensor.

• 4 x 24VAC or DC Isolated switched contact digital inputs.

Outputs:

• 2 x 24VAC or DC Relay Outputs, Normally Open contacts. Rated at 16 Amp Resistive, 6 Amp

Inductive.

• 3 x Analogue Output, 0-10VDC ±0.05V into > 2 kΩ load.

Figure 3-21:  GENII MP432 REM Multipoint Module

The RS485 Comms connection block is in the lower-left section of the module (as illustrated above) and

the End of Cable Jumper is next to it.

The unit must be powered down before jumpers are altered. Anti-static precautions should be taken when changing

addresses or adding or removing cabling from the terminals.