3-4.12 GENII CSAH REM Control Station A/H Module

The GENII CSAH REM is powered by 24VAC ±10% @ 50/60 Hz. Power Consumption is 3VA maximum.

The GENII CSAH REM mounts into a standard electrical wall plate. The only connections to the GENII

CSAH REM are 24VAC power and the RS485 Comms link. Locations of electrical terminals are shown

in Figure 3-16, which is a rear view of the module.

When all connections have been made, protect the module from dirt and moisture by covering it with

plastic but do not mount the module in the wall plate until commissioning is completed. This is to

allow addresses to be set as part of the commissioning process.