3 installation instructions, 3.1 din rails, Din rail dimensions – Innotech Genesis II Digital Controller (v5) User Manual

Page 26: E 2-10

Advertising
background image

Genesis II Installation Instructions

Page 26

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

2-3 Installation Instructions

A steel enclosure is recommended to contain the system with the aim of minimizing EMI from

surrounding equipment. To allow for the number of cables to enter and leave the enclosure, the

minimum dimensions of slotted cable ducts should be 45mm x 45mm with 65mm clearance from the

cable ducts to the terminals of the units.

The communications cable between the Genesis II Direct Digital Controller and REMs, or MPCII

Mid Points Controller and REMS, is through the integrated RS485 REM Comms port in the digital

controller.

ALL DIMENSIONS ARE IN MILLIMETRES

15

35

25

Mounting Slot

18 X 5.2

Unless otherwise noted, Installation Instructions are based on the assumption that the system to be installed is a

local Genesis II System consisting of one Genesis II Direct Digital Controller and three types of REMs. Installation

instructions for other types of hardware, such as the MPCII Mid Points Controller or GENII WMI Wireless Module

Interface, is contained in section

2-4 - Difference Data

.

NOTE

2-3.1 DIN Rails

The DIN rail is an industry-standard item and is available from a large number of commercial

sources. The rail is usually manufactured from galvanised steel and may be provided with a finish.

It is typically available in 2 metre lengths. DIN rail cutters are available commercially and are

recommended; however, for smaller installations, a hacksaw may be used to cut the rails to the

required length.

Figure 2-10 shows the dimensions of a typical DIN rail section.

Figure 2-10:  DIN Rail Dimensions

Advertising