Parameter 590 – [A>ChB DH Rd Wrd2]
Parameter 540 – [B>ChB DH Rd Wrd2]

Use: Channel B Read word 2
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 1
Default Value: 0

Description: Each node address can add two words of data to the global
data table which is passed with the network token. The data is then
available to other nodes on DH+ by specifing the originating node address
and the desired word. This parameter determines which of these two
words the DH TP In 2 parameter will receive its data from. The node
address is specified by the DH Rd Nde2 parameter.

Parameter 591 – [A>ChB DH Rd Nde3]
Parameter 541 – [B>ChB DH Rd Nde3]

Use: Channel B Read Station Number 3
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 77
Default Value: 8

Description: Each node address can add two words of data to the global
data table which is passed with the network token. The data is then
available to other nodes on DH+ by specifing the originating node address
and the desired word. This parameter specifies which node address the
DH TP In 3 parameter will receive its data from. The node address is
entered in octal so that it corresponds with the node addressing scheme of
DH+. The default value of 8 disables the data transfer.

Parameter 592 – [A>ChB DH Rd Wrd3]
Parameter 542 – [B>ChB DH Rd Wrd3]

Use: Channel B Read word 3
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 1
Default Value: 0

Description: Each node address can add two words of data to the global
data table which is passed with the network token. The data is then
available to other nodes on DH+ by specifing the originating node address
and the desired word. This parameter determines which of these two
words the DH TP In 3 parameter will receive its data from. The node
address is specified by the DH Rd Nde3 parameter.