Chapter 3

Configuration & Interfacing

3–6

Figure 3-3. Constant Parameter Example

550

Input
504

1000

Constant #1
550

Multiply #1 Block

MCA Board

By placing the constant #1 parameter number (Par #550) into the input
parameter (Par #504) the data value of 1000 in constant parameter (P #550)
is used as the input to the Multiply 1 block.

In this example a configuration link is made between the Drive’s velocity
feedback parameter (Par #106) and the Digital Communication adapter CA
Indirect #1 parameter (Par #364). Also, the CA Indirect #1 parameter
number is placed into the Input Parameter (Par #504) of the Multiply 1
block. Once these connections are made the Drive will provide the
velocity feedback value as an input to the Multiply 1 block.

Figure 3-4. CA Indirect parameter

364

Input
504

Velocity
Feedback

Multiply #1 Block

MCA Board

364

106

CA Indirect

#1

Configuration

Link

1395 Drive

315

Output