Chapter 3

Configuration & Interfacing

3–11

Add Block

General Description – The Add block (Figure 3–7) sums up to three
external values (parameters 508, 510, 512) and one offset value (parameter
514) to obtain a result. Each external input has a scale factor (parameters
509, 511, 513) that is independently programmable. The output (Par 318)
can be linked to other Drive parameters or used by other MCA function
blocks. The Overflow Control parameter (parameter 517) determines the
fault type and action taken when an overflow condition occurs.

Figure 3-7. Add Block

Offset

514

Add Block

Function Block

Overflow

517

318

Add

Output

R

1

+ R

2

+ R

3

+ C

4

R

1

0,1,8,9

R

2

R

3

C

4

Input #1

508

Input #1 Gain

509

Input #2

510

Input #2 Gain

511

Input #3

512

Input #3 Gain

513

Bits

Par Num

Description

318

508

509

510

511

512

513

514

517

Table 3-H.

Parameter Listing for Add Block

Output

Setup

Setup

Setup

Setup

Setup

Setup

Setup

Setup

Par Type

Add Block Output

Input #1

Input #1 Gain

Input #2

Input #2 Gain

Input #3

Input #3 Gain

Input Offset

Overflow Control Parameter