Rockwell Automation 1395 Multi-Comm Hardware/Software User Manual

Page 31

Advertising
background image

Chapter 3

Configuration & Interfacing

3–20

Bit numbering in the PLC Controller is performed in Octal, as opposed to
Decimal numbering in the Drive parameter 150, so it is necessary to relate
the output image table bits to the controlled bits in parameter 150. Figure
3–15 shows the correlation between the output image table bits and the
Drive parameter 150 bits. As a result of this relationship, if it is desired to
set the start bit in parameter 150 (bit 12 decimal), then bit 021/14 must be
set as shown in the first rung of Figure 3–14. Control of other logic bits is
illustrated in Figure 3–14.

Figure 3-15. Bit Mapping for Logic Command (P150, 151, 152)

Output Image Table

PLC Controller (Rack 2)

PORT A INTERFACE

150

Group 0

Group 1

Group 2

Group 3

Group 4

Group 5

Grpup 6

Group 7

Sinks

Port B

Sources

307

0 : 21

Logic Cmd 1

00
01
02
03
04
05
06
07

10
11
12
13
14
15
16
17

Par 150

00
01
02
03
04
05
06
07

08
09
10
11
12
13
14
15

Run Reference Select A
Run Reference Select B
Run Reference Select C

MOP Increment

MOP Decrement

Ramp Disable

MOP Rate 1
MOP Rate 2

Command Enable

Jog 2
Jog 1

Normal Stop

Start

Close Contactor

Clear Fault

Process Trim Enable

The first 3 bits of the Logic Command word (parameter 150 in this
example), are used to determine which speed reference will be used by the
Drive. If the normal run speed reference input to parameter 154 is to be
used, all three bits must be 0. If a preset speed or the MOP function will be
used, bits 0–2 are set accordingly (refer to Bulletin 1395 Installation and
Maintanance manual for a complete description of the Logic Command
bits). In this example, the first three bits of word 2 of integer file N7 are
used to determine the speed reference used by the Drive as shown on rung
4 in Figure 3–14.

Advertising