Autotune update motor inertia – Rockwell Automation 1395 Multi-Comm Hardware/Software User Manual

Page 67

Advertising
background image

Chapter 3

Configuration & Interfacing

3–56

Autotune Update Motor Inertia

This function updates the Drives internal database with the motor inertia
(parameter 613) calculated by the autotune firmware and provides the data
to the PLC Controller in the BTR message.

PLC Block Transfer Data

BTW Instruction Length: 4
BTR Instruction Length: 6

PLC DH+ Data –

Write

Read

Size In Elements:

4

6

Processor Type:

PLC–5

PLC–5

Destination Address

N15:0–3

N15:0–5

Message Structure –
Message Header Information:
Word 1
: 0
Word 2: 0
Function Code, Word 3: 525
Write Message Length, Word 4: 8 bytes

WORD

0

0

525

8

BTW

BTR

0

0

525

See Note

1

2

3

4

NOTE:

Word 4 of the BTR instruction is broken down into
two bytes. The High byte contains the status bits
per table 3–H. The low byte contains the Drive
message length in bytes.

Parameter 613

Parameter Data

5

6

Message Operation – The AUTOTUNE UPDATE MOTOR VELOCITY
function updates the Drives internal database with the motor inertia
(parameter 613) calculated by the autotune firmware and provides the data
to the PLC Controller in the BTR message.