Mca status word, Status word bit definitions – Rockwell Automation 1395 Multi-Comm Hardware/Software User Manual

Page 36

Advertising
background image

Chapter 3

Configuration & Interfacing

3–25

MCA Status Word

The status word is returned from the MCA Board to the PLC Controller in
addition to the Block Transfer Status Byte (Word 4, high byte). The MCA
status word appears as the first slot (or word) in the rack assigned to the
Multi-Communications Adapter (Refer to Figure 3–17). This status byte
indicates the condition of the MCA itself and is not included as part of the
PLC Controller block transfer instruction. However, individual bits from
this word are used in the PLC Controller program to control block transfer
instructions to the Drive. Refer to the block transfer example for proper
use of these bits.

Figure 3-17. DCSTATUS - Adapter Status Word Description

PLC Controller

Digital Communications Adapter

Rack 0
Rack 1
Rack 2



Rack U

Input Image
Table

Rack #2

DC STATUS

Word 1
Word 2
Word 3



Rack U

Decimal

Octal

15 14 13 12 11 10 9 8

17 16 15 14 13 12 11 10

7 6 5 4 3 2 1 0

7 6 5 4 3 2 1 0

BIT

Block Transfer Error (BT_ ERROR)

Block Transfer Wait (BT_ WAIT)

Block Transfer Read AVAIL (BT__ RD __ DATA __ AVAIL)

Block Transfer Write in Progress (BT__ WR __ IPROG)

Block Transfer Ready (BT__ Ready)

Channel in control when MCA is in Redundant mode.

Status Word Bit Definitions

Block Transfer Ready – Indicates that the Drive is ready to process and
receive block transfer requests.

IMPORTANT: Do not attempt to send block transfer requests to the Drive
if this bit is not set. The Drive will not respond to the request.

Advertising