Chapter 6

Troubleshooting

6–3

Action:

Check DIP switch settings and reset drive, if condition
persists replace adapter board.

Message:

CA–35–ADD FUNC BLK OVERFLOW

Fault Type: Warning/Soft
Cause:

The Add function block output value has overflowed.

Action:

Check range on inputs, gains values, and offset values for
ADD block.

Message:

CA–36–MULT1 FUNC BLK OVERFLOW

Fault Type: Warning/Soft
Cause:

The Multiplication function block output value has
overflowed.

Action:

Check input range and gain value.

Message:

CA–37–MULT2 FUNC BLK OVERFLOW

Fault Type: Warning/Soft
Cause:

The Multiplication 2 function block output value has
overflowed.

Action:

Check input range and gain value.

Message:

CA–44–ADAPTER PROCESSOR FAULT

Fault Type: Hard
Cause:

Adapter internal diagnostic malfunction.

Action:

Check dip switch settings and reset drive, if condition persists
replace adapter board.

Message:

CA–45–ADAPTER PROCESSOR FAULT

Fault Type: Hard
Cause:

Adapter internal diagnostic malfunction.

Action:

Check dip switch settings and reset drive, if condition persists
replace adapter board.

Message:

CA–50–ADAPTER PROCESSOR FAULT
CA–51–ADAPTER PROCESSOR FAULT
CA–52–ADAPTER PROCESSOR FAULT

Fault Type: Hard
Cause:

Adapter internal diagnostic malfunction.

Action:

Check dip switch settings and reset drive, if condition persists
replace adapter board.

Message:

CA–53–CHANNEL A BT FAIL
CA–54–CHANNEL B BT FAIL

Fault Type: Warning
Cause:

Unable to complete RIO block transfer.

Action:

Resend block transfer, if condition persists, replace adapter
board.