Service Aid

If service aids are available, you can use the Link Verification service aid to show that
the SSA loop is broken.

LINK VERIFICATION

802386

SSA Link Verification for:

systemname:ssa0

00-04

SSA Enhanced RAID Adapter

To Set or Reset Identify, move cursor onto selection, then press <Enter>.

Physical

Serial#

Adapter Port
A1 A2 B1 B2

Status

[TOP]

systemname:pdisk11

AC50AE43

0

5

Good

systemname:pdisk8

AC706EA3

1

4

Good

systemname:pdisk2

AC1DBE11

2

3

Failed

systemname:pdisk3

AC1DBEF4

3

2

Good

systemname:pdisk7

AC50AE58

4

1

Good

systemname:pdisk12

AC7C6E51

5

0

Good

systemname:pdisk0

AC706E9A

0

Good

?????

Good

systemname:pdisk10

AC1DBE32

3

Good

[MORE...4]

F3=Cancel

F10=Exit

This example screen shows a break in the SSA loop between the pdisk0 and pdisk10.
In the condition shown by the display, the Ready lights on the pdisk0 and pdisk10 are
both flashing.

To help locate these disk drives, select the pdisk, and press Enter. The Check light on
the selected disk drive flashes. This action does not affect the customer’s operations.

For more information about the service aids, see Chapter 17, “SSA Service Aids” on
page 373.

Repair Actions

When you have determined the parts of the failing link, check whether the cause of the
problem is obvious; for example, a loose cable connection, or a disk drive with its
Check light on. If the cause is obvious, correct it. If the cause is not obvious, exchange
the parts of the link, one at a time, until the problem is solved.