Rice Lake Static Weighing User Manual

Page 32

Advertising
background image

28

CW-90/90X Checkweigher

OVRBAS

CALIB
SCALE

Zero base for overload calculation.

CALIB = Calibrate Zero
SCALE = Scale Zero

AGENCY

NTEP
CANADA
INDUST
NONE
OIML

Selects the agency having jurisdiction over the scale site.

OIML, NTEP, and CANADA modes allow a tare to be acquired at any weight
greater than zero. NONE allows tares to be acquired at any weight value. A
tare can be cleared only if the gross weight is at no load. NONE allows tares
to be cleared at any weight value.

NTEP and OIML modes allow a new tare to be acquired even if a tare is
already present. In OIML mode, printing is not allowed if the scale is more
than -20dd.

In CANADA mode, the previous tare must be cleared before a new tare can
be acquired.

NONE, NTEP and CANADA modes allow the scale to be zeroed in either
gross or net mode as long as the current weight is within the specified
ZRANGE. In OIML mode, the scale must be in gross mode before it can be
zeroed; pressing ZERO in net mode clears the tare.

INDUST provides a set of subparameters to allow customization of tare,
clear, and print functions in non-legal-for-trade applications.

The value specified for this parameter affects the function of the front panel TARE and
ZERO keys. See Section 9.6 on page 64 for more information.

FEATUR Menu, REGULA / INDUST Submenu

Parameter

Choices

Description

Level 4, REGULA / INDUST submenu

Table 3-6. REGACY / INDUST Submenu Parameters (Continued)