20 SCT Weight Transmitter Operator’s Manual

Analog Output Type Scale Corrections

Minimum and maximum values which can be set for the zero and full scale corrections Refer to COr 0 and COr FS.

The analog output may also be used in the opposite manner, i.e. the weight setting that corresponds to the
analog zero may be greater than the weight set for the analog full scale. The analog output will increase
towards full scale as the weight decreases; the analog output will decrease as the weight increases.

E.g.: analog output type having selected 0-10V
ANA 0 = 10000 ANA FS = 0
Weight = 0 kg

analog output = 10 V

Weight = 5000 kg

analog output = 5 V

Weight = 10000 kg

analog output = 0 V

2.6

Profibus Settings

1. Press and hold

and

to enter set-up menu. CALIb will be displayed.

2. Press

or

until PrOFI is displayed, press

.

3. Addr is displayed, press

.

4. Press

or

until desired value is displayed, press

.

5. Press

twice to exit set-up menu.

Analog Output Type

Minimum

Maximum

0–10 V

-0.15

10.2

0–5 V

-0.15

5.5

-10 +10 V

-10.3

10.2

-5 +5 V

-5.5

5.5

0-20 mA

-0.2

22

4-20 mA

-0.2

22

Parameter

Choices

Description

Addr

1

-99

1 *

Set instrument address in the Profibus network.

* - indicates default value.

Note

Profibus