The instrument works as a slave in a DeviceNet network.
Load the included eds file (TLBDNT.eds) in the DeviceNet master’s development instrument.
The data exchanged by SCT20-DN are:

Possible Command To Send To The Command Register

If it is necessary to perform the same command twice in a row, send the command 0 between a command and
the other.

Gross Weight, Net Weight:

The weight values are expressed as positive integer numbers, including decimal figures but without decimal point.
Read the “Status Register” to obtain information about sign and possible errors on the weight.

Setpoints:

The Setpoints are weight values expressed as positive integer numbers, including decimal figures but without

decimal point.

• READING: send to the Command Register the reading command of the required setpoint (e.g. 90 for reading

setpoint 1) and read the content of the "Setpoint" register.

• WRITING: write the weight value to be set in the “Setpoint” and send to the Command Register, the writing

command of the required setpoint (e.g. 93 for writing setpoint 1).

Setpoints are stored to the RAM volatile memory and lost upon instrument power off. To save them
permanently in the EEPROM memory, so that they are maintained upon the instrument power on, it is
necessary to send the command 99 “Save data in EEPROM” of the Command Register.

Digital Inputs Status

Bit a 1: input high; Bit a 0: input is low

Outgoing Data from SCT20-DN (Read)

Addresses

Gross Weight [4 bytes]

0x0000-0x0003

Net Weight [4bytes]

0x0004-0x0007

Setpoint [4 bytes]

0x0008-0x000B

Status Register [2 bytes]

0x000C-0x000D

Digital Inputs Status [1 byte]

0x000E

Digital Outputs Status [1 byte]

0x000F

Input Data to SCT20-DN (Write)

Addresses

Command Register [2 bytes]

0x0000-0x0001

Digital Outputs Command [2 bytes]

0x0002-0x0003

Setpoint [4 bytes]

0x0004-0x0007

0

No command

90

Read setpoint 1

7

Semi-automatic tare (NET display)

91

Read setpoint 2

8

SEMI-AUTOMATIC ZERO

92

Read setpoint 3

9

GROSS display

93

Write setpoint 1

21 Keypad lock

94

Write setpoint 2

22 Keypad and display unlock

95

Write setpoint 3

23 Keypad and display lock

99

Save data in EEPROM

9999 Reset (reserved)

Bit 0

INPUT 1 status

Bit 4

Bit 1

INPUT 2 status

Bit 5

Bit 2

Bit 6

Bit 3

Bit 7