Rice Lake Signal Conditioning Transmitter/Indicators User Manual

Page 54

Advertising
background image

50 SCT Weight Transmitter Operator’s Manual

The output status can be read at any time but can be set (written) only if the output has been set as NOdbUS or

dEUnEt (see Section 2.10 on page 27); otherwise, the outputs will be managed according to the current weight
status with respect to the relevant setpoints.

Status Register (40007)

Bit 0

Cell Error

Bit 1

AD Convertor Malfunction

Bit 2

Maximum weight exceeded by 9 divisions

Bit 3

Gross weight higher than 110% of full scale

Bit 4

Gross weight beyond 999999 or less than -999999

Bit 5

Net weight beyond 999999 or less than -999999

Bit 6

Bit 7

Gross weight negative sign

Bit 8

Net weight negative sign

Bit 9

Peak weight negative sign

Bit 10

Net display mode

Bit 11

Weight stability

Bit 12

Weight within +/-¼ of a division around ZERO

Bit 13

Bit 14

Bit 15

INPUTS REGISTER (40029)

(Read Only)

OUTPUTS REGISTER (40030)

(Read and Write)

Bit 0

INPUT 1 Status

Bit 0

OUTPUT 1 Status

Bit 1

INPUT 2 Status

Bit 1

OUTPUT 2 Status

Bit 2

Bit 2

OUTPUT 3 Status

Bit 3

Bit 3

Bit 4

Bit 4

Bit 5

Bit 5

Bit 6

Bit 6

Bit 7

Bit 7

Bit 8

Bit 8

Bit 9

Bit 9

Bit 10

Bit 10

Bit 11

Bit 11

Bit 12

Bit 12

Bit 13

Bit 13

Bit 14

Bit 14

Bit 15

Bit 15

Note