12 ascii bidirectional protocol, See section 3.12), Section 3.12) – Rice Lake Signal Conditioning Transmitter/Indicators User Manual

Page 56

Advertising
background image

52 SCT Weight Transmitter Operator’s Manual

Possible Commands To Send To The Command Register (40006)

3.12 ASCII Bidirectional Protocol

All the sample commands use address 1. If a different address is used it will need a different Check-Sum
calculated.

The instrument replies to the requests sent from a PC/PLC.
It is possible to set a delay time for the instrument before it transmits a response (see dELAY parameter in Section

2.9 on page 24).
The following communication modes available (see Section 2.9 on page 24):

• NOdU60:
• NOd td:

Data Identifiers

$: Beginning of a request string (36 ASCII);

& o &&: Beginning of a response string (38 ASCII);

aa: 2 characters for instrument address (48 ÷ 57 ASCII);

!: 1 character to indicate the correct reception(33 ASCII);

?: 1 character to indicate a reception error (63 ASCII);

#: 1 character to indicate an error in the command execution (23 ASCII);

ckck: 2 ASCII characters for Check-Sum (for further information, see “Check-Sum Calculation” on

page 56);

CR: 1 character for string end (13 ASCII);

\: 1 character for separation (92 ASCII).

0

No command

17

Reserved

1

18

Reserved

2

19

3

20

4

21

Keypad lock

5

22

Keypad and display unlock

6

23

Keypad and display lock

7

NET display

24

8

SEMI-AUTOMATIC ZERO

99

Save data in EEPROM

9

GROSS display

100

Zero-setting for calibration

10

Reserved

101

Test weight storage for calibration

11

Reserved

12

Reserved

13

Reserved

14

Reserved

15

Reserved

16

Reserved

9999

Reset (reserved)

Note

Advertising
This manual is related to the following products: