30 SCT Weight Transmitter Operator’s Manual

2.12 Setpoints Programming

1. Press

to enter setpoints and hysteresis settings.

2. Press

or

until desired setpoint or hysteresis parameter is displayed, press

to enter.

3. Press

or

until desired value is displayed, press

to confirm.

4. Press

to exit setpoints and hysteresis settings.

These values are set to zero if the calibration is changed significantly (see Section 2.1.1 “Theoretical
Calibration” on page 13
and Section 2.1.5 “Weight (Span) Calibration (With Test Weights)” on page 15).

Parameter

Choices

Description

SEtP 1
SEtP 2
SEtP 3

0-Full Scale

0 *

Setpoint; relay switching occurs when the weight
exceed the value set in this parameter. The type of
switching is settable (see Section 2.10 “Outputs
And Inputs Configuration” on page 27
).

HYStE 1
HYStE 2
HYStE 3

0-Full Scale

0 *

Hysteresis, value to be subtracted from the
setpoint to obtain contact switching for decreasing
weight. For example with a setpoint at 100 and
hysteresis at 10, the switching occurs at 90 for
decreasing weight.

* - indicates default value.

Note