Coefficient display – Rice Lake Signal Conditioning Transmitter/Indicators User Manual
Page 42
38 SCT Weight Transmitter Operator’s Manual
Coefficient Display
The Profibus register contains the value of parameter COEFF, expressed as integer number, with 4 decimal figures
but without decimal point.
E.g.: If COEFF is 1.2000, the Profibus register contains 12000
Least significant byte
(L Byte)
Most significant byte
(H Byte)
Division
value Divisor
Decimals
Units of
measure
value
Units of
measure
description
Utilization of the Coefficient
value with the different units of
measure settings compared to
the gross weight detected
0
100
0
0
Kilograms Does
not
intervene
1
50
0
1
Grams Does
not
intervene
2
20
0
2
Tons Does
not
intervene
3
10
0
3
Pounds Does
not
intervene
4
5
0
4
Newton
Multiples
5
2
0
5
Litres
Divides
6
1
0
6
Bar Multiples
7
0.5
1
7
Atmsphere
s
Multiples
8
0.2
1
8
Pieces Divides
9
0.1
1
9
Newton
Meter
Multiples
10
0.05
2
10
Kilogram
Meter
Multiples
11
0.02
2
11
Other Multiples
12 0.01
2
13
0.005
3
14
0.002
3
15
0.001
3
16
0.0005
4
17
0.0002
4
18
0.0001
4