2 bcm (boiler communications module) fault codes, Gf-115-c, Modulex e8 controller and bcm – AERCO Modulex E8 Controls Guide User Manual

Page 106

Advertising
background image

PR1: 11/30/12

Page

106 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

10.2.2 BCM (Boiler Communications Module) Fault Codes

The table below shows how to interpret the displayed fault code, while Table 10-3, on the next

page, shows a description of the fault and troubleshooting tips associated with the BCM.

NOTE

In order to properly interpret a Fault Code for Modulex

Boilers, as displayed in the BCM (Boiler Communication

Module), it is necessary to refer to the table below in order

to determine the actual Fault Code that will be looked up in

the Fault Code table 10-3 on the following pages.

DISPLAYED

NUMBER

FAULT

NAME

FAULT CODE FORMULA

0

No Fault

None

Between

1 and 255

BMM #0 Fault Displayed Number = BMM Fault Code in Table 10-3

Between

256 and 511 BMM #1 Fault Subtract 256 from Displayed Number = BMM Fault Code in Table 10-3

Between

512 and 767 BMM #2 Fault Subtract 512 from Displayed Number = BMM Fault Code in Table 10-3

Between

768 and 1023 BMM #3 Fault Subtract 768 from Displayed Number = BMM Fault Code in Table 10-3

Between

1024 and 1279 BMM #4 Fault Subtract 1024 from Displayed Number = BMM Fault Code in Table 10-3

Between

1280 and 1535 BMM #5 Fault Subtract 1280 from Displayed Number = BMM Fault Code in Table 10-3

Between

1536 and 1791 BMM #6 Fault Subtract 1536 from Displayed Number = BMM Fault Code in Table 10-3

Between

1792 and 2047 BMM #7 Fault Subtract 1792 from Displayed Number = BMM Fault Code in Table 10-3

Between

2048 and

65279

Invalid Codes None

Above

65280

BCM Fault

Subtract 65280 from Displayed Number = BCM Fault Code in Table 10-3







Advertising