GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

9.2 BCM Controller Standard Holding Register Assignments

9.2.1 BCM Controller Standard Input Register Assignments

The BCM Controller has only two Read Only Input Register addresses as shown in

Table 9-3.

Table 9-3: BCM Controller Standard Input Register Address Mapping

Modbus

Data

Address

Menu Item

Units and Range

0

Status & Error Code

enum (2,8,10,18,23,32,42,38)

2 = Standby

8 = High temperature switch open

10 = Low gas pressure switch open

18 = Air flow switch open during

ignition

23 = Flame loss during run

32 = Residual flame

42 = Outlet temperature sensor fault

38 = Other conditions not listed above

1

Unit Status

enum (1, 3, 5)

1 = Standby (ready to run but not

fired)

3 = Remote (fired)

5 = Fault (failure detected)

9.2.2 BCM Controller Standard Holding Register Assignments

The BCM Controller Holding Registers contain functions that are Read Only, Write Only or both

Read & Write. The address assignments for these functions are listed in

Table 9-4 and are

grouped into the following major categories: Control Registers, Operating Data Registers,

System Data Settings and Test Registers. Functions within each group are not necessarily in

hex address order.
The Read Only, Write Only or Read/Write status for each function in

Table 9-4 is shown in the

Default/Comments column.