5 dhw operation using an aquastat, 1 sensor wiring connections, 3 setting the dhw set point – AERCO Modulex E8 Controls Guide User Manual

Page 55: 4 displaying temperatures associated with dhw, 6 boiler & pump enable/disable, Gf-115-c, Modulex e8 controller and bcm

Advertising
background image

PR1: 11/30/12

Page

55 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

5.5 DHW Operation Using an Aquastat

Operation, wiring connections and Controller configuration settings for DHW heating using an

aquastat are virtually identical to the procedures previously described in

paragraph 5.4 for the

tank sensor. Therefore, the following paragraphs describe only the differences between these

two types of applications.

5.5.1 Sensor Wiring Connections

To monitor the DHW temperature, connect the aquastat wire leads to Connector KF/SPF,

Terminals 6 (F6) and 7 (GND). After the sensor is connected, turn the ON/OFF switch to the

OFF position, then back to the ON position. This is necessary to ensure that the Controller

recognizes the added sensor.

IMPORTANT

The aquastat MUST be connected as described above, prior to

configuring the Controller for DHW operation. Also, the aquastat

must be closed (shorted) for the Controller to display the required

sub-menu functions.

5.5.2 Configuring the Controller for DHW With an Aquastat

The procedures for configuring the Controller for DHW with an Aquastat are virtually identical

to those specified in

paragraph 5.4.2. The only difference is that the THERM INPUT in the

EXPERT menu/HOT WATER sub-menu must be set to 01 (Aquastat) instead of 00 (Sensor).

5.5.3 Setting the DHW Set Point

Same as

paragraph 5.4.3.

5.5.4 Displaying Temperatures Associated With DHW

Same as

paragraphs 5.4.4 through 5.4.4.2.

5.6 Boiler & Pump Enable/Disable

The Enable/Disable feature found between terminals 3 and 4 of connector “I” can be used to

start/stop the boiler only in Indoor/Outdoor Reset and Constant Set Point modes of operation.

The Enable/Disable does not start/stop the boiler in 0 to 10 Volt Remote Set Point mode. To

start/stop the boiler in 0 to 10 Volt Remote Set Point mode, see

paragraph 5.3.4.

To use the Enable/Disable feature, wire a dry set of contacts between terminals 3 and 4 of

Connector “I” and then set the boiler to Standby mode ( ). To set the boiler to Standby

mode, close the swing-down front panel door of the E8 and turn the wheel counterclockwise

until the Standby symbol ( ) is displayed. With terminals 3 and 4 closed, the Standby

symbol, and others in the display, will be blinking. This indicates that the boiler is enabled.

When the connection is broken between terminals 3 and 4, the Standby symbol, and others in

the display, will stop blinking indicating that the boiler is disabled.
The Enable/Disable feature not only start/stops the boiler but also start/stops the pumps.